ꯂꯣꯁ ꯃꯦꯖꯔꯁꯤꯡꯗꯒꯤ ꯇ꯭ꯔꯥꯟꯁꯐꯣꯔꯃꯔꯒꯤ ꯏꯐꯤꯁꯤꯑꯦꯟꯁꯤ ꯑꯁꯤ ꯀꯔꯝꯅꯥ ꯂꯦꯄꯀꯅꯤ꯫

 May 19, 2026

 ꯄꯥꯎꯖꯦꯜ ꯑꯃꯥ ꯊꯥꯗꯣꯀꯎ

 

Q: ꯇꯦꯁ꯭ꯇꯁꯤꯡꯗꯒꯤ P₀ ꯑꯃꯁꯨꯡ Pₖ ꯄꯤꯔꯒꯥ, ꯇꯣꯉꯥꯟ-ꯇꯣꯉꯥꯅꯕꯥ ꯂꯣꯗ ꯂꯦꯚꯦꯂꯁꯤꯡꯗꯥ ꯑꯩꯅꯥ ꯀꯔꯝꯅꯥ ꯏꯐꯤꯁꯤꯑꯦꯟꯁꯤ ꯂꯦꯄꯀꯅꯤ?

 

A: ꯏꯐꯤꯁꯤꯑꯦꯟꯁꯤ η=P_out / (P_out + P₀ + 2 × Pₖ) × 100%, ꯃꯐꯝ ꯑꯗꯨꯗꯥ=ꯂꯣꯗ ꯐꯦꯛꯇꯔ꯫

ꯈꯨꯗꯝ ꯑꯣꯏꯅꯥ: 10 MVA ꯇ꯭ꯔꯥꯟꯁꯐꯣꯔꯃꯔ, P₀=12 kW, Pₖ=85 kW:

ꯄꯣꯠꯂꯨꯝ

ꯑꯥꯎꯠꯄꯨꯠ (ꯀꯤꯂꯣꯋꯥꯠ) ꯴.

ꯄꯤ ꯲ (ꯀꯤꯂꯣꯋꯥꯠ) ꯴.

꯲×ꯄꯤₖ (ꯀꯤꯂꯣꯋꯥꯠ) ꯴.

η (%)

25%

0.25

2,500

12

5.3

99.31

50%

0.50

5,000

12

21.3

99.34

75%

0.75

7,500

12

47.8

99.21

100%

1.00

10,000

12

85.0

99.04

120%

1.20

12,000

12

122.4

98.89

= √(P₀ / Pₖ)=0.376 → ~37.6% ꯂꯣꯗꯇꯥ ꯃꯦꯛꯁꯤꯃꯝ ꯏꯐꯤꯁꯤꯑꯦꯟꯁꯤ꯫

ꯏꯅꯔꯖꯤ ꯏꯐꯤꯁꯤꯑꯦꯟꯁꯤꯒꯤ ꯁ꯭ꯇꯦꯟꯗꯔꯗꯁꯤꯡ: ꯱.

• ꯑꯥꯏ.ꯏ.ꯁꯤ.꯶꯰꯰꯷꯶-꯲꯰: ꯏ.ꯏ.ꯑꯥꯏ.ꯒꯤ ꯀ꯭ꯂꯥꯁꯁꯤꯡ ꯑꯦ (ꯈ꯭ꯕꯥꯏꯗꯒꯤ ꯋꯥꯡꯕꯥ) → ꯗꯤ.

• ꯏꯌꯨ ꯏꯀꯣꯗꯤꯖꯥꯏꯟ ꯲꯰꯱꯹/꯱꯷꯸꯳: ꯇꯌꯥꯔ ꯲ (꯲꯰꯲꯱), ꯇꯌꯥꯔ ꯳ (꯲꯰꯲꯵–꯲꯷)꯫

• ꯗꯤ.ꯑꯣ.ꯏ.꯱꯰ ꯁꯤ.ꯑꯦꯐ.ꯑꯥꯔ.ꯒꯤ ꯄꯥꯔꯠ ꯴꯳꯱: ꯖꯨꯟ ꯲꯰꯲꯶ꯇꯒꯤ ꯆꯠꯅꯕꯥ ꯍꯧꯒꯗꯕꯥ ꯑꯅꯧꯕꯥ ꯔꯨꯜ꯫

• ꯖꯤ.ꯕꯤ.꯲꯰꯰꯵꯲-꯲꯰꯲꯰ (ꯆꯥꯏꯅꯥ): ꯒ꯭ꯔꯦꯗ ꯱ (ꯈ꯭ꯕꯥꯏꯗꯒꯤ ꯋꯥꯡꯕꯥ) → ꯳.

• ꯑꯥꯏ.ꯑꯦꯁ.꯱꯱꯸꯰ (ꯚꯥꯔꯠ): ꯕꯤ.ꯏ.ꯏ.ꯒꯤ ꯁ꯭ꯇꯥꯔ ꯔꯦꯇꯤꯡ ꯱–꯵꯫

ꯇꯤ.ꯁꯤ.ꯑꯣ.ꯒꯤ ꯑꯦꯞꯔꯣꯆ: ꯇꯤ.ꯁꯤ.ꯑꯣ.= ꯃꯃꯜ + ꯑꯦ × ꯄꯤ₀ + ꯕꯤ × ꯄꯤₖ꯫

A ≈ $3,000–8,000/kW (ꯅꯣ-ꯂꯣꯗ ꯀꯦꯄꯤꯇꯦꯂꯥꯏꯖ ꯇꯧꯔꯕꯥ ꯃꯃꯜ)꯫

B ≈ $500–2,000/kW (ꯂꯣꯗ ꯀꯦꯄꯤꯇꯦꯂꯥꯏꯖ ꯇꯧꯔꯕꯥ ꯃꯃꯜ)꯫

ꯏꯅꯛꯕꯥꯔꯤ ꯊꯥꯕꯤꯌꯨ
ꯏꯅꯛꯕꯥꯔꯤ ꯊꯥꯕꯤꯌꯨ