Q: ꯇꯦꯁ꯭ꯇꯁꯤꯡꯗꯒꯤ P₀ ꯑꯃꯁꯨꯡ Pₖ ꯄꯤꯔꯒꯥ, ꯇꯣꯉꯥꯟ-ꯇꯣꯉꯥꯅꯕꯥ ꯂꯣꯗ ꯂꯦꯚꯦꯂꯁꯤꯡꯗꯥ ꯑꯩꯅꯥ ꯀꯔꯝꯅꯥ ꯏꯐꯤꯁꯤꯑꯦꯟꯁꯤ ꯂꯦꯄꯀꯅꯤ?
A: ꯏꯐꯤꯁꯤꯑꯦꯟꯁꯤ η=P_out / (P_out + P₀ + 2 × Pₖ) × 100%, ꯃꯐꯝ ꯑꯗꯨꯗꯥ=ꯂꯣꯗ ꯐꯦꯛꯇꯔ꯫
ꯈꯨꯗꯝ ꯑꯣꯏꯅꯥ: 10 MVA ꯇ꯭ꯔꯥꯟꯁꯐꯣꯔꯃꯔ, P₀=12 kW, Pₖ=85 kW:
|
ꯄꯣꯠꯂꯨꯝ |
|
ꯑꯥꯎꯠꯄꯨꯠ (ꯀꯤꯂꯣꯋꯥꯠ) ꯴. |
ꯄꯤ ꯲ (ꯀꯤꯂꯣꯋꯥꯠ) ꯴. |
꯲×ꯄꯤₖ (ꯀꯤꯂꯣꯋꯥꯠ) ꯴. |
η (%) |
|
25% |
0.25 |
2,500 |
12 |
5.3 |
99.31 |
|
50% |
0.50 |
5,000 |
12 |
21.3 |
99.34 |
|
75% |
0.75 |
7,500 |
12 |
47.8 |
99.21 |
|
100% |
1.00 |
10,000 |
12 |
85.0 |
99.04 |
|
120% |
1.20 |
12,000 |
12 |
122.4 |
98.89 |
= √(P₀ / Pₖ)=0.376 → ~37.6% ꯂꯣꯗꯇꯥ ꯃꯦꯛꯁꯤꯃꯝ ꯏꯐꯤꯁꯤꯑꯦꯟꯁꯤ꯫
ꯏꯅꯔꯖꯤ ꯏꯐꯤꯁꯤꯑꯦꯟꯁꯤꯒꯤ ꯁ꯭ꯇꯦꯟꯗꯔꯗꯁꯤꯡ: ꯱.
• ꯑꯥꯏ.ꯏ.ꯁꯤ.꯶꯰꯰꯷꯶-꯲꯰: ꯏ.ꯏ.ꯑꯥꯏ.ꯒꯤ ꯀ꯭ꯂꯥꯁꯁꯤꯡ ꯑꯦ (ꯈ꯭ꯕꯥꯏꯗꯒꯤ ꯋꯥꯡꯕꯥ) → ꯗꯤ.
• ꯏꯌꯨ ꯏꯀꯣꯗꯤꯖꯥꯏꯟ ꯲꯰꯱꯹/꯱꯷꯸꯳: ꯇꯌꯥꯔ ꯲ (꯲꯰꯲꯱), ꯇꯌꯥꯔ ꯳ (꯲꯰꯲꯵–꯲꯷)꯫
• ꯗꯤ.ꯑꯣ.ꯏ.꯱꯰ ꯁꯤ.ꯑꯦꯐ.ꯑꯥꯔ.ꯒꯤ ꯄꯥꯔꯠ ꯴꯳꯱: ꯖꯨꯟ ꯲꯰꯲꯶ꯇꯒꯤ ꯆꯠꯅꯕꯥ ꯍꯧꯒꯗꯕꯥ ꯑꯅꯧꯕꯥ ꯔꯨꯜ꯫
• ꯖꯤ.ꯕꯤ.꯲꯰꯰꯵꯲-꯲꯰꯲꯰ (ꯆꯥꯏꯅꯥ): ꯒ꯭ꯔꯦꯗ ꯱ (ꯈ꯭ꯕꯥꯏꯗꯒꯤ ꯋꯥꯡꯕꯥ) → ꯳.
• ꯑꯥꯏ.ꯑꯦꯁ.꯱꯱꯸꯰ (ꯚꯥꯔꯠ): ꯕꯤ.ꯏ.ꯏ.ꯒꯤ ꯁ꯭ꯇꯥꯔ ꯔꯦꯇꯤꯡ ꯱–꯵꯫
ꯇꯤ.ꯁꯤ.ꯑꯣ.ꯒꯤ ꯑꯦꯞꯔꯣꯆ: ꯇꯤ.ꯁꯤ.ꯑꯣ.= ꯃꯃꯜ + ꯑꯦ × ꯄꯤ₀ + ꯕꯤ × ꯄꯤₖ꯫
A ≈ $3,000–8,000/kW (ꯅꯣ-ꯂꯣꯗ ꯀꯦꯄꯤꯇꯦꯂꯥꯏꯖ ꯇꯧꯔꯕꯥ ꯃꯃꯜ)꯫
B ≈ $500–2,000/kW (ꯂꯣꯗ ꯀꯦꯄꯤꯇꯦꯂꯥꯏꯖ ꯇꯧꯔꯕꯥ ꯃꯃꯜ)꯫